the main - Walls
  Filter gas designation on the diagram. Alphanumeric designations of gas pipelines. Types of documents BTI

This standard establishes the composition of the right to design working drawings for internal devices for gas supply * and the construction of all branches of industry.

* Inside  nnye devices gas  supplies are hereinafter referred to as gas supply.

1. GENERAL PROVISIONS

drawings (plans, sections, types and diagrams) of gas installations;

STATE STANDARD OF THE UNION SSR

SYSTEMSA DESIGN DOCUMENT FOR CONSTRUCTION

GAS SUPPLY.
  INTERNAL DEVICES

WORKING DRAWINGS

GOST 21.609-83

STANDARDS PUBLISHING HOUSE

Moscow

STATE STANDARD OF THE UNION SSR

This standard establishes the composition and design rules for working drawings of internal gas supply devices * for buildings and structures of all industries and national economy.

* Internal gas supply devices are hereinafter referred to as gas supply.

1. GENERAL PROVISIONS

1.1. Working drawings of gas supply are performed in accordance with the requirements of this standard and other standards of the design documentation system for construction, as well as the norms of gas supply design.

1.2. The composition of the working drawings of gas supply (the main set of working drawings of the brand FGP) include:

general data on the working drawings;

drawings (plans, sections and views) of the location of gas pipelines, gas instrumentation and gas equipment **;

gas supply schemes;

drawings (plans, sections, types and diagrams) of gas installations;

sketch drawings of common types of atypical devices and gas supply structures ***.

**   Gas instrumentation and gas equipment are hereinafter referred to as equipment.

*** Sketch drawings of general types of atypical devices and structures are hereinafter referred to as drawings of general types.

To the main set of working drawings of the GSV brand, the specification of the equipment and the list of material requirements in accordance with GOST 21.109-80 are performed.

Namee

Alphanumeric designation

1. Gas pipeline:

a) the general designation

b) low pressure up to 5 kPa

(0.05 kgf / cm 2 )

c) average pressure over

5 kPa (0.05 kgf / cm 2)

up to 0.3 MPa (3 kgf / cm 2)

d)   high pressure more

G 3

0.3 (3) to 0.6 MPa (6 kgf / cm 2)

d)   high pressure more

0.6 (6) to 1.2 MPa (12 kgf / cm 2)

2. Blowing gas pipeline

3. Pipeline for vacuum

1.4. The diameter and thickness of the wall of the pipeline indicate the line of the leader.

For gas pipelines made of steel water and gas pipes indicate the diameter of the nominal passage and wall thickness.

For gas pipelines from steel electrowelded and other pipes indicate the outer diameter and wall thickness.

In the case when the alphanumeric designation of a gas pipeline is indicated on the shelf of the leader line, its diameter and wall thickness are indicated under the shelf of the leader line.

1.5. The risers of gas pipelines are designated by the brand consisting of the letter designation “St” and, through a hyphen, the serial number of the riser within the building (structure), for example St-1, St-2.

1.6. Conditional graphic images of valves (shut-off, regulating and safety) and equipment are accepted according to state standards, taking into account the additional images given in.

Name

Picture

1. Gas meter

2. Household double-burner gas stove

3. Household four-burner gas stove

4. Gas heating appliance

5. Furnace heating and cooking

6. Gas fireplace

7. Pressure Regulator

8. Safety shut-off valve

9. Control Regulator

2. GENERAL DATA ON WORKING DRAWINGS

2.1. The general data of the main set of working drawings of the FGP brand in addition to the data provided for by GOST 21.102-79 include:

Key indicators for working drawings of the FGP brand

_________

* The characteristic of the gas used is indicated in a note.

3. DRAWINGS OF THE GAS PIPELINE
  AND EQUIPMENT

3.1. The drawings of the location of gas pipelines and equipment are performed in accordance with GOST 21.101 -79, taking into account the requirements of this standard.

3.2. Plans, cuts and types

3.2.1. Plans, sections and views are carried out on a scale of 1: 100 or 1: 200, nodes and fragments of plans, sections and types are carried out on a scale of 1:10 - 1: 100 according to GOST 2.302-68.

In case of small buildings or structures, when the execution of fragments is impractical, plans, sections and views are allowed to be carried out at the scales established for the fragments.

3.2.2. Pipelines located one above the other on the plans are conventionally represented by parallel lines.

3.2.3. Pipelines, equipment and fittings on plans, sections and views are indicated by conventional graphic images, and equipment for which conventional graphic images are missing are simplified graphic images.

Pipelines with a diameter of 100 mm and more on the fragments and nodes represent two lines.

3.2.4. On the plans, sections and views indicate: the coordination axis of the building (structure) and the distance between them (for residential buildings - the distance between the axes of the sections);

building structures and equipment to which gas-air is supplied and from which combustion products are diverted. Building structures and equipment indicate in continuous thin lines;

level marks for clean floors and main sites;

dimensional bindings of gas installations and equipment, inputs (outputs) and risers of gas pipelines to coordination axes or elements of building structures;

sizes of operational passes;

level marks or height adjustment installation of devices (if necessary).

The plans also indicate the names of the premises (types of premises for residential buildings) and the category of production for explosive, explosion-fire and fire danger (in a rectangle of size 5 ´ 8 mm), and on the cuts and types - the marks of the levels of the axes of gas pipelines and the top of the waste gas pipeline (candles).

The names of the premises and the category of productions for explosive, explosion-fire and fire danger are allowed to be given in the explication of the premises according to Form 2 of GOST 21.501 -80.

The plans and sections of the location of household equipment (gas stoves, water heaters) in residential buildings, utility enterprises and public buildings provide data on the volume and height of the room in which this equipment is installed, and also indicate the location of the chimneys (their section) and the location of the ventilation lattices.

An example of a design plan is shown in, cut in and view of.

4. SCHEMES OF GAS SUPPLY

The scale of the images is according to GOST 2.302-68: for schemes 1: 100 or 1: 200, nodes of schemes 1:10 - 1:50, schemes for small buildings (structures) 1:20 - 1:50.

4.2. Pipelines and fittings in the diagrams are indicated by conventional graphic images, and equipment that lacks a conventional graphic image is indicated by a simplified graphic image.

For residential and public buildings, instead of a graphic image of the connected equipment, it is allowed to indicate its name.

4.3. With a large distance and (or) a complex arrangement of gas pipelines it is allowed to depict them with a gap in the form of a dotted line. Locations of gas line breaks are designated by lowercase letters.

Heck. 2

Heck. 3

4.4. On the diagrams indicate:

equipment, fittings, gas pipelines and their diameters;

places of attachment of devices (lugs);

elevations of axes of gas pipelines;

slopes of gas pipelines (for wet and liquefied petroleum gas);

dimensions of horizontal sections of gas pipelines in the presence of gaps;

gas pipelines and their designations.

An example of the design scheme is shown in.

5. DRAWINGS OF GAS INSTALLATIONS

5.1. Plans, sections, types and schemes of gas installations (hereinafter - installations) are carried out on a scale of 1:50 or 1: 100, units of installations are on a scale of 1: 2 - 1:20 according to GOST 2.302-68.

5.2. On the plans, sections and views, the elements of the installations are represented simply.

If it is necessary to show the methods of fastening the components of the installation or their connection among themselves, the corresponding elements of the installation are depicted in detail.

On the installation diagrams, the installation elements are indicated by conventional graphic images (in the axonometric image).

5.3. On the plans, sections and types of installations indicate:

the coordination axis of the building (structure) and the distance between them;

main dimensions, level marks and binding of installations to the coordination axes of the building (structure).

5.4. Pipelines in the plans, sections and types of installations depict a single line with a diameter of the pipeline up to 100 mm and two lines - with a diameter of more than 100 mm.

5.5. On the plans, sections and views, in addition to the elements of the installations, indicate the building structures with a solid thin line and selective devices (bosses) for the installation of instruments.

production part;

auxiliary part.

If a residential building has an extension or building in which public service enterprises are located, then each section of the specification is made up in parts:

residential part;

attached (built-in) part.

The name of each part is written in the form of a heading in column 2 of the specification and underline.

7.3. In the sections (parts) of the specification, elements are written in the following sequence:

equipment;

fittings;

gas pipelines for each diameter. Elements of gas pipelines (elbows, transitions, flanges, bolts, nuts, washers, etc.) do not include in the specification;

materials.

7.4. The specification takes the following units:

gas pipelines - m;

fittings - pcs .;

insulating materials - m 3;

coating and protection materials - m 2;

other materials - kg.

1. Scheme of the gas network in a semi-detached house

2. The diameters in the gas network supplying the meters with one apartment with a bathroom on the floor; with two apartments on the floor.

3. Sizes of niches for 1 - 3 gas meters. OKF - clean floor level.

4. Niche for 1 electric and 1 gas meter.

5. Niche for 1 electric and 1 gas meter.


6. The room of inputs of engineering networks (DIN 18012) with the turning on and locking devices for strong and weak currents, gas, water supply and the sewerage.

7. Section of the premises of utilities engineering networks.

8. Layout of premises utilities utilities.

The following devices do not require connection to the gas ducts:

1. All types of gas cookers and gas refrigerators.

2. Heaters with a capacity of up to 10 liters in rooms with a volume of at least tenfold gas consumption.

3. Tanks for boiling linen and washing machines with a gas consumption of up to 2.5 m3 / h in rooms with a volume of at least tenfold gas consumption.

4. Gas heaters installed at the exterior walls with exhaust holes in the wall.

In all other cases (water heaters, laundry boilers and larger washing machines, heating stoves, etc.), gas appliances must be connected to gas ducts.

The supplier is obliged to install a fuse on the outlet nozzle, which eliminates the possibility of condensation and the return of exhaust gases. The automatic dimmer valve of the Dirmeyer system with thermal regulation (Fig. 2) protects the premises from cooling through the flue duct and from violation of the thrust when the exhaust duct is mixed (for off-gases from gas and solid-fuel appliances); in addition, such a valve reduces noise. The carbon dioxide content in the air of rooms designed for temporary stay of people (bathroom, kitchen, etc.) should not exceed 0.4%; in rooms for a long stay (common rooms and bedrooms) about 0.15%.

Flues

No more than three firing points are allowed to be connected to the standard-section gas duct of 135 x 135 mm in brick walls: do not make gas ducts with a cross section of more than 200 x200 mm; firing points operating on solid fuel and gas, if possible, do not attach to one gas duct. Ducts should be located in warm places to avoid condensation on the cold walls. On the top of the flue, you must install a wind cap. On flat roofs, ducts should be no less than 50 cm above the parapet (Fig. 3 and 4).

Gas consumption: for taking a shower for 5 minutes with a water heater with a capacity of 5 liters - 0.25 m3; for heating the room for 15 minutes - 0.25 m3.

Liquefied gas (non-toxic gases - propane, butane, etc.) is used for gas supply in remote areas.

Specifications for liquefied gas (TRF 1969):

Capacity Mass in the filled state, kg Diameter, mm Height mm Height with valve, mm
Small cylinders 3 205 320 420
5 230 400 500
11 300 500 600
Large cylinders 22 270 1100 1200
33 320 1200 1300

Places for installation of cylinders: small cylinders can be installed in any room except sleeping rooms; large cylinders - outside the building in a lockable metal cabinet or in a room with a separate external entrance; 1 kg of liquefied gas (3 m3 of natural gas) gives about 5000kkal.

Liquefied gas costs almost 1/3 more than gas from the city network.

The diameters of pipes with liquefied gas are significantly less than the diameters of gas pipes of the city network due to increased pressure.

When a property, for example, an apartment building, is put into operation, it is necessary to inventory it in order to legally fix the available space. To this end, employees of the Bureau of Technical Inventory measure the premises. And further, on the basis of the data obtained, make up the floor plan of the building.

However, to coordinate the redevelopment of the floor plan of the building is not needed, it is enough to have a floor plan of the apartment or the non-residential premises, which is planned to alter. Thus, it can be said that the floor plan or simply the BTI plan is a document of information and reference type, where, taking into account the measurements, the actual state of the apartment (non-residential premises) is presented.

The BTI plan shows the exact size of the rooms and graphically marks the following elements:

  • main walls and partitions;
  • balconies and loggias;
  • door and window openings;
  • sanitary appliances and cookers;
  • ventilation.

All of these elements are marked in the BTI floor plan.

Types of documents BTI

The following types of documents issued by the Bureau of Technical Inventory are used to coordinate redevelopment.

Floor plan and explication

You can learn more about what these documents are, how and where they can be ordered from a separate articles  . Here we only note that these are the simplest documents of the BTI, in which the minimum information about the object is presented.

The floor plan is a diagram of the object, presented as a drawing with special symbols. At the entrance to the apartment on the drawing indicated her number. In addition, the sheet contains a stamp of the BTI office, which issued the document. Also, the BTI floor plan contains information on the legal address of the building and the floor on which the room is located, as well as the date of its last survey.

An explication is attached to the floor plan, which lists and assigns all the premises of the object - residential and auxiliary - with an indication of their area and height of ceilings.

Floor plan with explication

Thus, the floor plan with explication is two sheets of the same format, one of which reflects the floor plan in the form of a drawing, and the other shows a table with the characteristics of the rooms and rooms.

Technical passport BTI

The technical passport is a document that is specifically designed to coordinate redevelopments.

Technical passport with BTI plan

About him we also have a separate one. But speaking in general, this is a more detailed document that, in addition to the floor plan and explication, contains information about the house where the room is located (series, material of walls and floors, number of floors of the building, number of apartments, year of construction, etc.) address plan, etc.

Floor plan with explication before redevelopment

This document is used to legitimize the redevelopment that has already been made, if illegally carried out changes are indicated in the BTI documents with red lines. Read more about this.

In general, this document is similar to a floor plan with explication, but it has a special mark “before redevelopment” or “before re-equipment”.

Floor plan with explication before redevelopment

Any room consists of structural elements that have their own name, purpose, size, shape and other characteristics. On the plans of the BTI, they are reflected in the form of conventional graphic symbols, which are not always clear to the owners of the premises.

And since everyone who has decided to redevelop his apartment and wants to make it legally will need to deal with some of these documents, it is important to be able to figure out how and what is indicated on them. Therefore, we will further analyze the notation on the BTI plans.

Description of designations on BTI plans

Immediately, we note that the designation BTI does not depend on the type of document. That is, one or another element of the drawing is denoted in the same way both in the data sheet and on the floor plan.

First of all, the owners are interested in such a question, how is the designation of the bearing walls on the BTI plan? Many consider that on the drawing thick walls mark capital walls, and thin - non-bearing partitions. But this is not always the case.

Therefore, it is impossible to determine according to the BTI plan which walls are bearing and which are non-bearing. In any case, it certainly can not make the man in the street themselves, if only he turns for help to a specialist.

If the room was completed uncoordinated redevelopment  , which became known to the BTI, then after the necessary measurements by an employee of the Bureau of Technical Inventory, all changes made in the drawing will be marked with red lines.

Doorways are indicated as follows: within the boundaries of the line, two small marks in the form of parallel dashes are applied perpendicularly to indicate the partition. In the presence of a door leaf between them, another parallel line extends beyond the wall boundary. That is the designation of the door on the BTI plan.

Similarly, information on the presence and location of window openings is entered into the floor plan. The thickest lines in the drawing are the facade walls, on which the windows are marked by two parallel lines with perpendicular constraints on both sides, showing their width.

The numbering and area of ​​the room are displayed as a fractional number, where the numerator is the room number and the denominator is its area.

In addition, the plans for BTI is applied to the location of plumbing and stoves in the "wet" areas of the apartment. Most often, it is possible to guess which plumbing fixtures are indicated in the drawing along the contours of the geometric shapes that designate them. And the designation of the electric stove on the BTI plan can also be guessed.

For reference:   furniture, refrigerator, air conditioner, washing machine and dishwasher, heated towel rail, oven, etc. not indicated on the BTI floor plan. Also has no designation in the passport BTI flooring material in the premises.

The interpretation of the notation on the BTI plan is the easiest to give with specific examples.

If you need to find out the symbols of BTI, as well as require assistance in the development of project documentation and the coordination of redevelopment in government agencies, our employees are always ready to help.

  equipment.
Working drawings

GOST
21.609-83

By the Decree of the USSR State Committee on Construction Affairs dated August 17, 1983 No. 203, the introduction date was set

from 01/01/84

a) common her label  ation

b) low pressure  up to 5 kPa

(0,05 kgf / cm 2)

c) wed day pressure more

5 kPa (0.05 kgf / cm 2)

up to 0.3 MPa (3 kgf / cm 2)

2. Wireline purge

3. Drain line niya

In the case when on the shelf callout lines  indicate the letter nn  The o-digital designation of the pipeline, its diameter and wall thickness indicate under the shelf callout lines.

1.5. Gas pipeline risers are designated by the brand name "St"  and, through a hyphen, the serial number of the riser within the building (structure), for example St-1, St-2.

1.6. The conditional graphic depicts reinforcement (shut-off, regulating and safety) and the equipment is accepted according to the state standard, taking into account the additional images given in.

Name

Picture

1. Gas meter

2. Household double-burner gas stove

3. Household four-burner gas stove

4. Gas heating appliance

5. Furnace heating and cooking

6. Gas fireplace

7. Pressure Regulator

8. Safety shut-off valve

9. Control Regulator

2. GENERAL DATA ON WORKING DRAWINGS

2.1. The general data of the main set of working drawings of the FGP brand in addition to the data provided for include:

Key indicators for working drawings of the FGP brand

_________

* The characteristic of the gas used is indicated in a note.

3. DRAWINGS OF THE GAS PIPELINE
  AND EQUIPMENT

3.1. Drawings for the location of gas pipelines and equipment are performed according to -79, taking into account the requirements of this standard.

3.2. Plans, cuts and types

3.2.1. Plans, sections and views are carried out on a scale of 1: 100 or 1: 200, nodes and fragments of plans, sections and types are carried out on a scale of 1:10 - 1: 100.

In case of small buildings or structures, when the execution of fragments is impractical, plans, sections and views are allowed to be carried out at the scales established for the fragments.

3.2.2. Pipelines located one above the other on the plans are conventionally represented by parallel lines.

3.2.3. Pipelines, equipment and fittings on plans, sections and views are indicated by conventional graphic images, and equipment for which conventional graphic images are missing are simplified graphic images.

Pipelines with a diameter of 100 mm and more on the fragments and nodes represent two lines.

3.2.4. On the plans, sections and views indicate: the coordination axis of the building (structure) and the distance between them (for residential buildings - the distance between the axes of the sections);

building structures and equipment to which gas-air is supplied and from which combustion products are diverted. Building structures and equipment indicate in continuous thin lines;

level marks for clean floors and main sites;

dimensional bindings of gas installations and equipment, inputs (outputs) and risers of gas pipelines to coordination axes or elements of building structures;

sizes of operational passes;

level marks or height adjustment installation of devices (if necessary).

The plans also indicate the names of the premises (types of premises for residential buildings) and the category of production for explosive, explosion-fire and fire danger (in a rectangle of size 5 ´ 8 mm), and on the cuts and types - the marks of the levels of the axes of gas pipelines and the top of the waste gas pipeline (candles).

The names of the premises and the category of production for explosive, explosion-fire and fire danger are allowed to be given in the explication of the premises in form 2 -80.

4. SCHEMES OF GAS SUPPLY

For residential and household buildings, instead of a graphical image of the connected equipment, it is allowed to indicate it.

Heck. one

Heck. 2

Pr m p clearance c we are given on

  Graphic symbols   Title   Reference to standard
  Gas pipeline common designation   GOST 21.609-83
  Low pressure gas pipeline, up to 5 kPa (0.05 kgf / cm2)   GOST 21.609-83
  Medium pressure gas pipeline, up to 0.3 MPa (3 kgf / cm2)   GOST 21.609-83
  High pressure gas pipeline, up to 0.6 MPa (6 kgf / cm2)   GOST 21.609-83
High pressure gas pipeline, up to 1.2 MPa (12 kgf / cm2)   GOST 21.609-83
  Gas purge   GOST 21.609-83
  Vacuum pipe   GOST 21.609-83
  Gas pipeline security   STP 3-76-89
  Gas meter   GOST 21.609-83
  Household double-burner gas stove (dvukhkonforochnaya)   GOST 21.609-83
  Three-burner household gas stove (three-burner)   GOST 21.609-83
  Household four-burner gas stove (four-burner)   GOST 21.609-83
  Gas heating appliance   GOST 21.609-83
  The furnace is heating and cooking   GOST 21.609-83
  Gas fireplace   GOST 21.609-83
  Pressure regulator   GOST 21.609-83
  Safety shut-off valve   GOST 21.609-83
  Control knob   GOST 21.609-83
  temperature sensor   GOST 21.404-85
  Showing thermometer   GOST 21.404-85
  Pressure meter   GOST 21.404-85
  Showing manometer   GOST 21.404-85
  Differential pressure sensor   GOST 21.404-85
  Showing differential meter   GOST 21.404-85
  Pressure switch   GOST 21.404-85
  Filter   GOST 21.205-93
  Heater   GOST 21.205-93
  Cooler   GOST 21.205-93
  Cooler and heater (thermostat)   GOST 21.205-93
  Heat recovery unit   GOST 21.205-93
  Steam Trap (Condensation Pot)   GOST 21.205-93
  Selection device for installation of the instrumentation on the pipeline)   GOST 21.205-93
  Solenoid valve   GOST 21.205-93
  Electro-Actuated Valve   GOST 21.205-93
  Flow direction   GOST 21.205-93
  Gas flow direction
  Isolated pipeline section   GOST 21.205-93 GOST 2.784-96
  Pipeline in pipe (case)   GOST 21.205-93 GOST 2.784-96
  Pipeline in the gland   GOST 21.205-93 GOST 2.784-96
  Control tube on the case of the pipeline   STP 3-75-89
  Place of resistance in the pipeline (throttle washer, flow constriction)   GOST 21.205-93 GOST 2.784-96
  Valve (gate) gate valve   GOST 21.205-93 GOST 2.784-96
  The valve (valve) locking angular   GOST 21.205-93 GOST 2.784-96
  Valve (valve) three-way   GOST 21.205-93 GOST 2.784-96
  The valve (gate) regulating a checkpoint   GOST 21.205-93 GOST 2.784-96
  Crane ball in the underground version (in the well)
  Crane ball in the underground version (under the carpet)   STO GAZPROMREGIONGAZ 1.2-2009
  Angle Regulating Valve (Valve)   GOST 21.205-93 GOST 2.784-96
  Check valve checkpoint   GOST 21.205-93
  Angle check valve   GOST 21.205-93
  Safety check valve   GOST 21.205-93
  Angle safety valve
  Throttle valve   GOST 21.205-93 GOST 2.785-96
  Reducing valve (the top of the triangle should be directed towards the increased pressure)   GOST 21.205-93 GOST 2.785-96
  Gate valve   GOST 21.205-93 GOST 2.785-96
  Gate valve in the underground version (in the well)   STO GAZPROMREGIONGAZ 1.2-2009
  Gate valve in the underground version (under the carpet)   STO GAZPROMREGIONGAZ 1.2-2009
  Butterfly valve   GOST 21.205-93 GOST 2.785-96
  Checkpoint crane   GOST 21.205-93 GOST 2.785-96
  Corner crane   GOST 21.205-93 GOST 2.785-96
  Three way crane   GOST 21.205-93 GOST 2.785-96
  Receiver   GOST 2.780-96
  Four way crane   GOST 2.785-96
  The valve is a non-return valve   GOST 2.785-96
  Valve irrevocably locking angular   GOST 2.785-96
  Valve non-return-controlled   GOST 2.785-96
  Self-closing valve   GOST 2.785-96
  High-speed shut-off valve for opening   GOST 2.785-96
  High-speed shut-off valve for closing   GOST 2.785-96
  Starting valve   GOST 2.785-96
  Double seat valve   GOST 2.785-96
  Valve to gauge   GOST 2.785-96
  Safety alarm valve   GOST 2.785-96
Clap without forced closure   GOST 2.785-96
  Forced closing   GOST 2.785-96
  The device limiting gas flow (UORG) in the aboveground performance   STO GAZPROMREGIONGAZ 1.2-2009
  Device for limiting gas consumption (OURG) in the underground version   STO GAZPROMREGIONGAZ 1.2-2009
  Flexible piping
  Flange joint   GOST 21.206-93 GOST 2.784-96
  Coupling threaded   GOST 21.206-93 GOST 2.784-96
  Quick-release coupling coupling   GOST 21.206-93
  Socket bell   GOST 21.206-93
  Transition   GOST 21.206-93 GOST 2.784-96
  Compensator common designation   GOST 21.205-93 GOST 2.784-96
  Compensator U-shaped   GOST 21.205-93 GOST 2.784-96
  Compensator lyroobrazny   GOST 2.784-96
  Lens compensator   GOST 2.784-96
  Lens compensator on flanges   STP 3-75-89
  Wavy compensator   GOST 2.784-96
  Compensator Z-shaped   GOST 2.784-96
  Bellows expansion joint   GOST 2.784-96
  Ring-shaped compensator   GOST 2.784-96
  Telescopic compensator   GOST 2.784-96
  Depreciation insert   GOST 2.784-96
  Soundproofing insert   GOST 2.784-96
  Electrically insulating insert   GOST 2.784-96
  Fixed support (toe) of the pipeline   GOST 21.205-93 GOST 2.784-96
  Mobile support (subsock) of the pipeline   GOST 21.205-93 GOST 2.784-96
  Ball bearing   GOST 2.784-96
  Support guide   GOST 2.784-96
  Sliding support   GOST 2.784-96
  Katkovy support   GOST 2.784-96
  Elastic support   GOST 2.784-96
  Fixed suspension   GOST 2.784-96
  Suspension guide   GOST 2.784-96
  Elastic suspension   GOST 2.784-96
  Pipeline on supports on the building wall   STP 3-75-89
  Gas riser   STP 3-75-89
  Hydraulic shock absorber   GOST 2.784-96
  Pneumatic or hydraulic actuated valve   GOST 2.721-74
  Pipeline sbrostnoy (candle)   STO GAZPROMREGIONGAZ 1.2-2009
  Artificial barriers (railway)   STO GAZPROMREGIONGAZ 1.2-2009
  Crossing gas pipelines without connection   STO GAZPROMREGIONGAZ 1.2-2009
  Pipeline connection - outlet   STO GAZPROMREGIONGAZ 1.2-2009
  Pipeline connection - tee   STO GAZPROMREGIONGAZ 1.2-2009
  Pipeline connection - cross   GOST 21.206-93
  Pipeline intersection without connection   GOST 21.206-93
  The connection elements of the pipeline - one-piece   STO GAZPROMREGIONGAZ 1.2-2009
  Connection of elements of the gas pipeline - one-piece (flange)   STO GAZPROMREGIONGAZ 1.2-2009
  Flanged, insulating   STP 3-75-89
  Oblique   STP 3-75-89
  Picket   STP 3-75-89
  The intersection of g / n natural obstacles - underwater transition (Duker)   STO GAZPROMREGIONGAZ 1.2-2009
  The intersection of g / p natural obstacles - surface transition (bridge)   STO GAZPROMREGIONGAZ 1.2-2009
  The end of the pipeline with a stove box (stopper)   STO GAZPROMREGIONGAZ 1.2-2009
  The end of the pipeline with a plug on the thread   STP 3-75-89
  Gas pipeline with vertical riser downward, upward   STO GAZPROMREGIONGAZ 1.2-2009
  Carpet   STO GAZPROMREGIONGAZ 1.2-2009
  Water lock   STO GAZPROMREGIONGAZ 1.2-2009
  Gas well   STO GAZPROMREGIONGAZ 1.2-2009
  Condensate collector   STO GAZPROMREGIONGAZ 1.2-2009
  Control tube   STO GAZPROMREGIONGAZ 1.2-2009
  Measuring point (for field conditions)   STP 3-75-89
  Measuring point (within the boundaries of the settlement)   STP 3-75-89
  Gas pipeline liquid phase liquefied gas   STP 3-75-89
  Gas pipeline   STO GAZPROMREGIONGAZ 1.2-2009
  The boundaries of the shifted area, the boundary of operational responsibility, the boundary of the protection zone of the CPS, etc.   STO GAZPROMREGIONGAZ 1.2-2009
  Hydraulic fracturing   STO GAZPROMREGIONGAZ 1.2-2009
  SHRP   STO GAZPROMREGIONGAZ 1.2-2009
  GDS promising (projected)   STO GAZPROMREGIONGAZ 1.2-2009
  GDS existing   STO GAZPROMREGIONGAZ 1.2-2009
  Control and distribution point   STO GAZPROMREGIONGAZ 1.2-2009
  Existing gas consumers   STO GAZPROMREGIONGAZ 1.2-2009
  Perspective gas consumers   STO GAZPROMREGIONGAZ 1.2-2009
  Gas sampling point   STO GAZPROMREGIONGAZ 1.2-2009
Pipeline damage   STO GAZPROMREGIONGAZ 1.2-2009
  Insulation damage   STO GAZPROMREGIONGAZ 1.2-2009
  Basement   STO GAZPROMREGIONGAZ 1.2-2009
  Deep Anode Earthing   STO GAZPROMREGIONGAZ 1.2-2009
  Anode grounding, surface, projected   STO GAZPROMREGIONGAZ 1.2-2009
  Anode grounding, surface, existing   STO GAZPROMREGIONGAZ 1.2-2009
  Joint protection unit   STO GAZPROMREGIONGAZ 1.2-2009
  Polarized, designed drainage   STO GAZPROMREGIONGAZ 1.2-2009
  Polarized, existing drainage   STO GAZPROMREGIONGAZ 1.2-2009
  Electrical drainage, projected   STO GAZPROMREGIONGAZ 1.2-2009
  Electrodrainage reinforced existing   STO GAZPROMREGIONGAZ 1.2-2009
  Drain cable being designed   STO GAZPROMREGIONGAZ 1.2-2009
  Existing drain cable   STO GAZPROMREGIONGAZ 1.2-2009
  Safety ground   STO GAZPROMREGIONGAZ 1.2-2009
  Contact device designed   STO GAZPROMREGIONGAZ 1.2-2009
  Contact device, existing   STO GAZPROMREGIONGAZ 1.2-2009
  Measuring station, projected   STO GAZPROMREGIONGAZ 1.2-2009
  Test point existing   STO GAZPROMREGIONGAZ 1.2-2009
  Control conductor KU   STO GAZPROMREGIONGAZ 1.2-2009
  0.4 kV overhead transmission line.   STO GAZPROMREGIONGAZ 1.2-2009
  Support VL 4-6 kV.   STO GAZPROMREGIONGAZ 1.2-2009
  Protector, projected (protector protection)   STO GAZPROMREGIONGAZ 1.2-2009
  Protector group, projected (protector protection)   STO GAZPROMREGIONGAZ 1.2-2009
  Existing protector (protector protection)   STO GAZPROMREGIONGAZ 1.2-2009
  Protector group, existing (protector protection)   STO GAZPROMREGIONGAZ 1.2-2009
  Potential measuring point   STO GAZPROMREGIONGAZ 1.2-2009
  Projected cathodic protection station   STO GAZPROMREGIONGAZ 1.2-2009
  Existing cathodic protection station   STO GAZPROMREGIONGAZ 1.2-2009
  Transformer substation, cabinets, etc.   STO GAZPROMREGIONGAZ 1.2-2009
  Electroinsulating flange connection (FIS)   STO GAZPROMREGIONGAZ 1.2-2009
  Electrically insulating one-piece connection (IFS)   STO GAZPROMREGIONGAZ 1.2-2009
  Electric jumper unregulated   STO GAZPROMREGIONGAZ 1.2-2009
  Choke transformer   STO GAZPROMREGIONGAZ 1.2-2009
  Control wire output on PE gas pipeline   STO GAZPROMREGIONGAZ 1.2-2009
  GOST 21.501-93
  Vents and ducts   GOST 21.501-93
  GOST 21.501-93
  Smoke pipes (solid fuel)   GOST 21.501-93
  Smoke pipes (solid fuel) at a scale\u003e 1: 200   GOST 21.501-93
  Smoke pipes (solid fuel) at a scale\u003e 1: 200   GOST 21.501-93
  GOST 21.501-93
  Smoke pipes (liquid fuel)   GOST 21.501-93
  GOST 21.501-93
  Venting pipes (flue)   GOST 21.501-93
  Ventilation deflector (duct)   ANSI / ASHRAE Standard 134-2005
  Window with a vent

GAS NETWORKS. SYMBOLS

Symbols of gas equipment. Explanation of accepted terminology. Color pipelines on the drawings. The diameters of the supply pipelines and gas costs for different devices. Gas ducts. Technical conditions for liquefied gas. Device of gas ducts.

1. The intersection of the gas network lines with open wiring 2. Recessed wiring 3. Changing the diameters of the gas network pipes 4. Air duct 5. Pulse pipe 6. Grounding 7. Gas hose 8. Ceiling lamp with indication of the number of horns 9. Fixed wall lamp 10. Wall Mobile lamp 11. Venting pipe 12. Flue 13. Gas stove with three burners 14. Gas stove with oven 15. Refrigerator 16. Gas heating stove 17. Flow-through water heater 18. Capacity water heater 19. Install the appliance in the opening with 20. Installation of the device in the opening with a gap of 21. Water bag, water tank 22. Wall mounted gas heater 23. Gas meter

Explanations to the accepted terminology:

gas appliances  named devices that do not require connection to the ducts;

gas firing points called devices that are connected to the ducts;

the instructions “up to the counter” and “behind the counter” correspond to the direction of gas movement in the network.

Gas consumption: for every 1 m3 of air volume in a heated room for the heating season (September - May) with a long fire (in residential buildings) 18 - 25 m3 of gas, with a periodic fire (in commercial premises) - 10 - 15 m3 of gas.

The color of the pipelines in the drawings: gas pipelines - yellow, cold water pipelines - light blue, hot water pipelines - red.

The diameters of the supply pipelines and gas costs for different devices:

1. Scheme of the gas network in a semi-detached house

2. The diameters in the gas network supplying the meters with one apartment with a bathroom on the floor; with two apartments on the floor.

3. Sizes of niches for 1 - 3 gas meters. OKF - clean floor level.

4. Niche for 1 electric and 1 gas meter.

5. Niche for 1 electric and 1 gas meter.

The following devices do not require connection to the gas ducts:

1. All types of gas cookers and gas refrigerators.

2. Heaters with a capacity of up to 10 liters in rooms with a volume of at least tenfold gas consumption.

3. Tanks for boiling linen and washing machines with a gas consumption of up to 2.5 m3 / h in rooms with a volume of at least tenfold gas consumption.

4. Gas heaters installed at the exterior walls with exhaust holes in the wall.

In all other cases (water heaters, laundry boilers and larger washing machines, heating stoves, etc.), gas appliances must be connected to gas ducts.

The supplier is obliged to install a fuse on the outlet nozzle, which eliminates the possibility of condensation and the return of exhaust gases. The automatic dimmer valve of the Dirmeyer system with thermal regulation (Fig. 2) protects the premises from cooling through the flue duct and from violation of the thrust when the exhaust duct is mixed (for off-gases from gas and solid-fuel appliances); in addition, such a valve reduces noise. The carbon dioxide content in the air of rooms designed for temporary stay of people (bathroom, kitchen, etc.) should not exceed 0.4%; in rooms for a long stay (common rooms and bedrooms) about 0.15%.

Flues

No more than three firing points are allowed to be connected to the standard-section gas duct of 135 x 135 mm in brick walls: do not make gas ducts with a cross section of more than 200 x200 mm; firing points operating on solid fuel and gas, if possible, do not attach to one gas duct. Ducts should be located in warm places to avoid condensation on the cold walls. On the top of the flue, you must install a wind cap. On flat roofs, ducts should be no less than 50 cm above the parapet (Fig. 3 and 4).

Gas consumption: for taking a shower for 5 minutes with a water heater with a capacity of 5 liters - 0.25 m3; for heating the room for 15 minutes - 0.25 m3.

Liquefied gas (non-toxic gases - propane, butane, etc.) is used for gas supply in remote areas.

Specifications for liquefied gas (TRF 1969):

Places for installation of cylinders: small cylinders can be installed in any room except sleeping rooms; large cylinders - outside the building in a lockable metal cabinet or in a room with a separate external entrance; 1 kg of liquefied gas (3 m3 of natural gas) gives about 5000kkal.

Liquefied gas costs almost 1/3 more than gas from the city network.

The diameters of pipes with liquefied gas are significantly less than the diameters of gas pipes of the city network due to increased pressure.

9. Diagram of a gas network connected to compressed gas cylinders

Created on the basis of:
  1. STO GAZPROMREGIONGAZ 1.2-2009 "Graphic display of gas distribution facilities and related communications."
  2. GOST 2.780-96 “Unified system for design documentation. Symbols conditional graphic. Air conditioning conditioners, hydraulic and pneumatic tanks. "
  3. GOST 2.784-96 “Unified system for design documentation. Symbols conditional graphic. Elements of pipelines.
  4. GOST 2.787-71 “Unified system for design documentation. Conditional graphic designations in schemes. Elements, devices and devices of the gas chromatograph system ".
  5. GOST 21.609-83 “System of project documentation for construction. Gas supply. Internal devices. Working drawings".
6. GOST 21.404-85 “System of project documentation for construction. Automation of technological processes. Designations conventional instruments and automation tools in the schemes ".
  7. GOST 21.206-93 "System of project documentation for construction. Symbols of pipelines ".



 


Read:



Objects of inanimate nature Examples of the influence of inanimate nature factors on plants

Objects of inanimate nature Examples of the influence of inanimate nature factors on plants

The influence of the environment on the body. Any organism is an open system, which means it receives substance, energy, information from outside, and thus ...

Finishing joinery

Finishing joinery

The book contains reference materials related to the manufacture and installation of woodwork and construction products and the production of household furniture. Cited ...

Block breakdown in AutoCAD - simple and effective teams from practitioners

Block breakdown in AutoCAD - simple and effective teams from practitioners

If an attempt to blow up a block in AutoCAD using the Explode command (_explode) does nothing, and the command line displays the message "Do not ...

Procurement and installation of instruments and automation systems

Procurement and installation of instruments and automation systems

Page 2 of 2 Installation of cable sleeves and seals refers to hidden works, therefore, the scope of as-built documentation includes a cutting magazine ...

feed-image RSS feed